<< Click to Display Table of Contents >> Navigation: »No topics above this level« 9.0 Operation |
The ECD SmartDRY™ Cabinet has been pre-programmed to meet the requirement of J-STD 033 for the safe storage of Moisture Sensitive Components, no additional programming is required. However, should you wish to review these setting or make changes to the setting to meet some other requirements, this can be done using the Menu System for programming the Cabinet. The complete list of the programmable features are described below.
The SmartBAKE™ is an optional feature OF MODEL SD-10SB. This section includes how to access SmartBAKE™ Menu options. If your ECD SmartDRY™ Cabinet does not include the SmartBAKE™ Module the menu BUTTON IS DIMMED. |
To enter the Main Menu press the Menu button. Use the buttons to select a desired option. To exit the screen, select the Back button which takes you “Back” to the previous menu.
The Menu System, if left unattended, will time out and return to the Main Display. |
When accessing options that require a Passcode the system default Passcode is 314. As you enter protected options, you will be prompted to enter it using the Up or Down buttons. Once selected, all locked options remain “unlocked” until you return to the Main Display.
|
Access to all programmable features start at the Main Menu. Both SmartDRY™ and SmartBAKE™ mode controls as well as other general settings can be accessed.
To access the SmartDRY™ Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the SmartDRY™ Settings by pressing the Dry button. |
The dry RH value that ECD SmartDRY™ is set to maintain. SmartDRY™ mode is a dryer and thus can only remove moisture from the interior of the cabinet. Drying stops when the measured RH reaches the set point and resumes when the measured RH value rises 0.5% above the set point.
To access the RH Setpoint setting:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the SmartDRY™ Settings by pressing the Dry button. |
2) | Select the RH Setpoint field to make active. Use the Up or Down button to adjust the desired set point. |
3) | Once completed, select the OK button to accept the new value. |
An Alarm can be set on both the RH and Temperature values in the SmartDRY™ mode. These alarms are independent of the alarms that can be set in the optional SmartBAKE™ mode – Model SD-10SB only. Both the RH and Temperature alarms are an “over limit” type, meaning, the alarm will sound when the measured value rises above the set Alarm value. A delay time can also be set for both the RH and Temperature alarms. This means the alarm will NOT sound until the alarm condition has been met for at least the programmed delay time. The alarm limits have been preprogrammed however are not enabled. Once the Cabinet has stabilized at set point, the alarms can be enabled. This is the only alarm required by J-STD 033 to monitor the RH level. You may also want to explore the other Alarms: SmartDRY™ Temperature, SmartBAKE™ RH, and SmartBAKE™ Temperature, enabling them as you wish.
The delay timer for the RH alarm will count down, not reset, when the measured value falls below the alarm value and before the delay time is reached. This count down is in1/10th time, in accordance with and as described in J-STD-033, “Short Duration Exposure” for the worst the case MSL component “floor life clock reset”. Thus, if the interior RH value of the cabinet rises above the alarm value (say, because the door is open) for 25 seconds, once the door is closed and the RH returns to below the alarm value, the delay timer will take 250 seconds to count back to 0. The delay timer for the temperature alarm will count down at a 1 to 1 rate when the measured value falls below the alarm value and before the delay time is reached. |
To access the Alarms Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the SmartDRY™ Settings by pressing the Dry button. |
2) | Select the Alarms button to enter the Alarms Menu. Select RH or Temp alarm button. |
3) | Select the RH Setpoint field to make active. Use the Up or Down buttons to adjust the desired value. |
4) | Once completed, select the OK button to accept the new value. |
The SmartBAKE™ process has two settable parameters: Temperature (30C to 60C) and time. These can be automatically calculated and set, based on the component being baked or manually set. To automatically calculate the correct Bake Temperature and time, select the J-STD-033 menu item and select the components MSL, its thickness range, and the time exposure past the floor life. SmartBAKE™ sets the bake temperature and time for you. To manually select the bake temperature and time, select Manual Bake.To access the SmartBAKE™ Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the SmartBAKE™ Menu by pressing the Bake button. |
2) | Select a desired menu item. |
To access the J-STD-33 Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the SmartBAKE™ Menu by pressing the Bake button. |
2) | Select the J-STD button to enter the J-STD-033 settings screen. Edit the desired settings selecting the OK button to accept each edited value. |
To access the Manual Bake Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the SmartBAKE™ Menu by pressing the Bake button. |
2) | Select the Manual button to enter the Manual settings screen. Edit the desired settings selecting the OK button to accept each edited value. |
An Alarm can be set on both the measured Temperature value and the measured RH value in the SmartBAKE™ Mode. These Alarms are independent of the alarms that can be set in the SmartDRY™ mode. Both the Temperature and RH alarms are an “over limit” type, meaning, the alarm will sound when the measured value rises above the set Alarm value. A delay time can also be set for both the Temperature and RH alarms. This means the alarm will NOT sound until the alarm condition has been met for at least the programmed delay time.
The delay timer for the RH alarm will count down, not reset, when the measured value falls below the alarm value and before the delay time is reached. This count down is in1/10th time, in accordance with and as described in J-STD-033, “Short Duration Exposure” for the worst the case MSL component “floor life clock reset”. Thus, if the interior RH value of the cabinet rises above the alarm value (say, because the door is open) for 25 seconds, once the door is closed and the RH returns to below the alarm value, the delay timer will take 250 seconds to count back to 0. The delay timer for the temperature alarm will count down at a 1 to 1 rate when the measured value falls below the alarm value and before the delay time is reached. |
To access the Alarms Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the SmartBAKE™ Menu by pressing the Bake button. |
2) | Select the J-STD or Manual button. |
3) | Select the Alarms button to enter the Alarms Menu. Select RH or Temp alarm button. |
4) | Select the RH Setpoint field to make active. Use the Up or Down buttons to adjust the desired value. |
5) | Select the ON/OFF toggle and OK button to make active. |
Other Settings menu contains general/global settings for the ECD SmartDRY™ Cabinet that are used to support the basic operation of both the drying and baking operations.
The units of temperature can be set for either ºC or ºF.
To access the Units settings:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Other Settings menu by pressing the Settings button. |
2) | Select the Units button to enter the Units settings screen. Select the Units field to make active. Use the Up or Down button to adjust the desired value. |
3) | Once completed, select the OK button to accept the new value. |
The date and time was set at the factory and is maintained by a battery backup. For proper time display on the graph view, the time zone and daylight savings time mode can be set for your location. You can also select 12 or 24 hour time format.
To access the Date/Time Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Other Settings menu by pressing the Settings button. |
2) | Enter the Date/Time Settings menu by pressing the Date button. Edit the desired settings selecting the OK button to accept each edited value. |
The time between logging is set to 6 minutes (10 reading per hour) at the factory. This can be changed to any value between 1 and 60 minutes. The internal memory uses a first in/first out (FIFO) storage method and can store up to 8,000 RH/Temp measurements or Events, such as Alarms or Power lose, etc. This is sufficient for about 30 days of recorded history before the oldest data starts to be deleted as new data is logged.
To access the Data Logging Menu:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Other Settings menu by pressing the Settings button. |
2) | Enter to the Log Settings by pressing the Log button. Select the Log Interval field to make active. Use the Up or Down button to adjust the desired value. |
3) | Once completed, select the OK button to accept the new value. |
THE LOG SCREEN PROVIDES ACCESS TO CLEAR THE stored memory. Performing this step clears unwanted data and starts logging data new data from this point on. |
The Network IP Address, Subnet Mask, Gateway and MAC Address are viewed here.
To access the Network Settings:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Other Settings menu by pressing the Settings button. |
2) | Enter the Network Settings by pressing the Network button. |
The RH/Temperature probe is calibrated independent of the ECD SmartDRY™ Cabinet. It's calibration constants and serial number are stored in the probe itself. These settings can be viewed here.
To access the RH/Temp Sensor Settings:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Other Settings menu by pressing the Settings button. |
2) | Enter the Sensor Settings by pressing the Sensor button. |
There are three automatic lighting controls that can be set or disabled: the Door switch Status and yellow to green threshold. With the Door switch set to yes, the white interior LEDs will automatically turn on when the door is open. Set to no, and the door switch will no longer cause the white interior LEDs to turn on when the door is opened. With the Status set to yes, the current status of the cabinet is shown by the LEDs in the interior lighting. Set to no, and the interior LEDs no longer show the current cabinet status.
YELLOW TO GREEN THRESHOLD SETS THE RH LEVEL ABOVE THAT SET POINT. STATUS LIGHTS CHANGE FROM YELLOW TO GREEN WHERE RH VALUE EXCEEDS SET POINT AFTER THE DOOR WAS OPENED. |
To access the Lighting Settings:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Other Settings menu by pressing the Settings button. |
2) | Enter the Lighting Settings by pressing the Lighting button. Edit the desired settings selecting the OK button to accept each edited value.. |
The Passcode can be changed to prevent unauthorized changes to the programming of the ECD SmartDRY™ Cabinet. You need the default Passcode listed in the beginning of this section to make this change.
To access the Passcode settings:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Other Settings menu by pressing the Settings button. |
2) | Enter the Passcode Settings by pressing the Passcode button. Select the Passcode field to make active. Use the Up or Down button to adjust the desired value. Once completed, select the OK button to accept the new value. |
3) | Select the ON/OFF toggle and OK button to make active. |
Help list the contact information at ECD and shows the current firmware program version number.
To access the Help Information:
1) | From the Main Display, enter the Main menu by pressing the Menu button. enter the Help screen by pressing the Help button. |
2) | To exit the screen, select the Back button which takes you “Back” to the previous menu. |
The Graph allows you to see the recorded measurements of either RH or Temperature in graphical form.
To view a graph:
1) | From the Main Display, enter the Graph menu by pressing the Graph button. Press the desired graph type. |
2) | Press the Left or Right button to scroll the graph forward or backward in time. |
3) | To exit the screen, select the Back button which takes you “Back” to the previous menu. |